This input base is part of the Modicon Momentum range, an offer of controller and IP20 monoblock I/Os for distributed control architecture. This analog input base offers 4 inputs with a full 16bit signed resolution. It offers differential analog input ranges from ±100mV, ±25mV. There is an isolation between channels and bus, channels and ground at 500V AC. It is furnished with 2 removable terminal blocks for electrical connection. It features 4 LEDs for channel status signaling. Its dimensions are 141.5mm (width) x 47.5mm (depth) x 125mm (height). It weighs 0.215kg. The main application of this module is infrastructures and energy, material handling, simple machine control. This product is certified by CE, FM Class 1 Division 2, CSA and UL. It is suitable for wall mount. Momentum is a flexible, modular family of components that easily snaps together and can be configured for a wide range of distributed I/O and control applications. System with 4 fundamental components that easily snap together in various combinations to form versatile control systems or sub-systems.Main Characteristic Value(s) Range of Product Modicon Momentum automation platform Product or Component Type Analogue input base Analogue input number 4 Analogue Input Type Differential Analogue Input Range +/- 100 mV 15 bits + sign > 10000 kOhm+/- 25 mV 15 bits + sign > 10000 kOhm Thermocouple type Thermocouple EThermocouple SThermocouple KThermocouple NThermocouple BThermocouple RThermocouple JThermocouple T Complementary Characteristic Value(s) Data format Full 16 bits signed Absolute accuracy error +/- 21 µV 77 °F (25 °C) +/- 25 mV+/- 27 µV 77 °F (25 °C) +/- 100 mV+/- 46 µV 140 °F (60 °C) +/- 25 mV+/- 94 µV 140 °F (60 °C) +/- 100 mV Temperature probe type Ni 100 0.125 mA +/- 25 mVNi 1000 0.125 mA +/- 100 mVPt 100 0.125 mA +/- 25 mVPt 1000 0.125 mA +/- 100 mV Update time 500 ms Isolation between channels 400 V DC Isolation between channels and ground 500 V AC for 1 minute Isolation between supply and ground 500 V for 1 minute Permissible common mode voltage 100 V DC between channels to ground115 V AC single or three phases between channels200 V DC between channels250 V AC between channels to ground250 V AC single phase between channels Common mode rejection 120 dB DC between channels130 dB 50 Hz AC between channels135 dB DC between channels to ground140 dB 60 Hz AC between channels145 dB 50 Hz AC between channels to ground155 dB 60 Hz AC between channels to ground Serial mode rejection 35 dB 50 Hz AC45 dB 60 Hz AC External power requirement +/- 30 V DC Maximum power dissipation in W 5.5 W Reverse polarity protection Internal Protection type Internal 2 A slow-blow Associated fuse rating 500 mA, fast blow Marking CE Local signalling 4 LEDs for channel status Electrical connection 2 connectors for removable terminal blocks Current consumption 305 mA 24 V DC Depth 1.9 in (47.5 mm) Height 4.9 in (125 mm) Width 5.6 in (141.5 mm) Product Weight 0.474 lb(US) (0.215 kg)