3-3C Metal Clad (MC) Cable with #6 Ground, Aluminum Armored, Stranded Copper Conductors Applications:Branch, feeder or service power distribution in commercial, industrial, institutional and multi-residential buildings. Lighting, power, control and signal circuits. • Fished or embedded in plaster, concealed or exposed installations. Environmental air handling spaces per NEC 300.22 (C).Places of assembly and theaters.Under raised floors for technology equipment conductors and cables.Installation in cable tray and approved raceways.Class I Div.2, Class II Div.2, Class III Div. 1 Hazardous Locations.Voltage rating for all applications is not to exceed 600 Volts. Construction:Type MC cables are constructed of soft-drawn bare copper with lead-free THHN/THWN-2 rated at 90˚C dry and available in sizes #14 AWG through and including #2 AWG, and including the green insulated ground conductor. The conductors are cabled, wrapped completely in a Mylar binder tape with an aluminum tape interlocked sheath applied over the entire assembly Standards:•ASTM B-3, B-8 and B-787UL 83, UL 1569, UL 1581 and UL 2556NEC 2014 : 300.22 (C), 310.10, 330,392, 518, 520, 530, 645NFPA 70Federal Specification A-A59544IEEE 1202 (70,000 BTU/hr) Vertical Flame Test/FT4CT Rated for 600 Volts if installed per the NEC directivesRated for 1 and 2 hour Through PenetrationRoHS CompliantARRA 2009 Buy American Compliant Specifications*: Conductors: 3 + 1 Ground (4 total conductors)Size: 3 AWG Ground Size: 6 AWGOutside Diameter: 1.009 inchesWeight: 1.175 per ft. *Data provided on this page is subject to change based on different manufacturers variances.