input module CPX-8DE-D With channel oriented diagnosis. Dimensions W x L x H=(* (incl. interlinking block and connection technology), * 50 mm x 107 mm x 50 mm), No. of inputs=8, Diagnosis=- Short circuit/overload per channel, Parameters configuring=(* - Input debounce time, * - Signal extension time, * - Behaviour after short circuit, * Module monitoring), LED displays=(* - 1 Group diagnosis, * - 8 Channel diagnosis, * - 8 Channel status) Dimensions W x L x H (incl. interlinking block and connection technology)50 mm x 107 mm x 50 mm No. of inputs 8 Diagnosis '- Short circuit/overload per channel Parameters configuring '- Input debounce time- Signal extension time- Behaviour after short circuitModule monitoring LED displays '- 1 Group diagnosis- 8 Channel diagnosis- 8 Channel status Input debounce time 3 ms (0.1 ms, 10 ms, 20 ms, parameterisable) Protection (short circuit) Internal electronic fuse protection per channel Operating voltage range DC 18 ... 30 V Intrinsic current consumption at operating voltage Typically 15 mA Max. residual current inputs per module 0.7 A Nominal operating voltage DC 24 V Electrical isolation channel – internal bus No Electrical isolation channel – channel No