KC characters KC EMC Nominal width pressurization 6 mm Exhaust nominal width 4.5 mm Type code VPPM Actuation type Electrical Sealing principle Soft Mounting position Any Design Pilot-controlled diaphragm regulator Short-circuit protection For all electrical connections Safety instructions VPPM safety position: if the supply cable breaks, the outlet pressure is maintained in uncontrolled form. Symbol 995303 Reverse polarity protection for all electrical connections Reset method Mechanical spring Type of control Pilot-controlled Valve function 3-way proportional pressure control valve Display type LED Pressure regulation range 0.06 bar ... 6 bar Inlet pressure 1 0 bar ... 8 bar Max. pressure hysteresis 0.03 bar Standard nominal flow rate 900 l/min DC operating voltage range 18 V ... 30 V Max. current consumption 300 mA Duty cycle 1 Protocol I-PortIO-Link® Residual ripple 0.1 Operating medium Inert gasCompressed air as per ISO 8573-1:2010 [7:4:4] Information on operating and pilot media Operation with oil lubrication not possible CE marking (see declaration of conformity) As per EU EMC directive Corrosion resistance class (CRC) 2 - Moderate corrosion stress Temperature of medium 10 °C ... 50 °C Degree of protection IP65 Ambient temperature 0 °C ... 60 °C Certification c UL us - Listed (OL)RCM compliance mark Product weight 400 g Linearity error FS 0.01 Temperature coefficient 0.04 %/K Repetition accuracy FS 0.005 IO-Link®, protocol version Device V 1.1 IO-Link®, communication mode COM1 (4.8 kBd), COM2 (38.4 kBd), COM3 (230.4 kBd) IO-Link®, port class A IO-Link®, process data width OUT 2 Byte IO-Link®, process data width IN 2 Byte IO-Link®, minimum cycle time 0.5 ms Type of mounting With accessoriesOptionally:With through-hole Pneumatic connection 1 Sub-base Pneumatic connection 2 Sub-base Pneumatic connection 3 Sub-base Note on materials RoHS-compliant Housing material AnodizedWrought aluminum alloy