Features Universal AC input / Full range Built-in active PFC function Alarm signal for AC OK and Battery low(via relay) Protections: Short circuit / Overload / Over voltage / Over Temperature Battery low protection/ Battery reverse polarity protection by fuse Cooling by free air convection -20 ~ + 70℃ wide operating temperature Can be installed on DIN rail TS-35/7.5 or 15 DC output voltage adjustable (+20%) LED indicator for power on Operating altitude up to 5000 meters (Note.6) 3 years warranty General Specification AC input voltage range 90~264VAC; 127~370VDC AC inrush current Cold start 35A at 115VAC, 70A at 230VAC DC adjustment range ±8.6% rated output voltage Overload protection 105%~150% constant current limiting, auto-recovery Over-voltage protection 115%~140% rated output voltage Setup, rise, hold up time 2000ms, 30ms, 20ms Withstand voltage I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC Working temperature -20~+70°C Vibration 10~500Hz, 2G 10min./1cycle, period for 60min. Each along X, Y, Z axes Safety standards UL62368-1, Dekra BS EN/EN62368-1, EAC TP TC 004, AS/NZS 62368.1 approved EMC standards EN55032 class B, EN61000-3-2,3, EN61000-4-2,3,4,5,6,8,11 Connection I/P: 3 poles, O/P: 8 poles screw DIN terminal Dimension (LxWxH) 63x125.2x115 Packing 12pcs / 10.5kg