Description: Monitor fluid levels by comparing conductivitymeasurements to adjusted set point. Theoutput relay becomes energized when fluidrises to the high probe. The relay remainsenergized until the liquid falls below the lowprobe. Used for PUMP DOWN applications. Features: - Single or dual point control- Fast-on connections- Power available LED- Double power fast-ons Options: - 24 VAC input power- Stainless steel probes- Multiple probe, pipe plugs- Power slave relays- Snap- track quick mounting hardware- A.C.T. will modify controls to provide thebest solution for your application. Specifications: - Board size 3” by 3”- Set point hysteresis 3%- Temperature range +32OF to 125OF- Supply voltage 120 VAC- Relay contacts 10 amps. SPDT- Power consumption 4.5 watts- Sensitivity range 50,000 ohms