カテゴリ: 論文誌(論文単位)グループ名: 【B】電力・エネルギー部門発行日: 2024/12/01タイトル(英語): Impacts of Quadrature-axis Equivalent Circuit Model of Turbine Generator on Simulation Results of Frequency Change in Grid Fault著者名: 青木 廉((一財)電力中央研究所),天野 博之((一財)電力中央研究所)著者名(英語): Ren Aoki (Central Research Institute of Electric Power Industry), Hiroyuki Amano (Central Research Institute of Electric Power Industry)キーワード: タービン発電機,横軸リアクタンス,周波数変化率,インバータ脱落 turbine generator,quadrature-axis reactance,rate of change of frequency,inverter trip要約(英語): In power system dynamic analysis, especially voltage analysis at load disconnection, it is known that the turbine generator model considering quadrature axis transient reactance Xq' (called LGT =5 in CRIEPI's Power System Analytical Tools (CPAT)) is more accurate than ignoring Xq' (called LGT =4 in CPAT). However, in power system analysis in Japan, LGT =4 seems to be used as the model for the turbine generator rather than LGT =5. It seems to be primarily because there is no significant difference between them in rotor angle stability analysis. However, it is not clear whether there is great difference between them in the analysis on the inverters trip in grid fault. In such an analysis, the change of frequency of inverters connection node is mainly important. In this paper, the impacts of Xq' of the turbine generator on the frequency change after grid fault are investigated. Through the time-domain simulations, it was found that the frequency change in grid fault of LGT =4 tend to be larger than that of LGT =5, indicating that there is a clear difference between the results of frequency analysis using LGT =4 and LGT =5.本誌: 電気学会論文誌B(電力・エネルギー部門誌) Vol.144 No.12 (2024)本誌掲載ページ: 616-625 p原稿種別: 論文/日本語電子版へのリンク: https://www.jstage.jst.go.jp/article/ieejpes/144/12/144_616/_article/-char/ja/