Application Application field installation Electrical data Operating voltage [V] 26.5...31.6 DC Max. current consumption from AS-i [mA] 230 Max. current load total [A] 4 Integrated watchdog yes Inputs / outputs Number of inputs and outputs Number of digital inputs: 4; Number of digital outputs: 4 Inputs Number of digital inputs 4 Input circuit of digital inputs PNP Sensor supply of the inputs AS-i Voltage supply [V] 20...30 Max. total current rating of inputs [mA] 200 Input current High [mA] > 5 Input current low [mA] < 3 Switching level high [V] > 10 Digital inputs protected against short circuits yes Outputs Number of digital outputs 4 Circuit PNP Voltage range DC [V] 24; (to PELV) Max. current load per output [mA] 1000; (DC-12 / DC-13) Short-circuit proof yes Electrically separated yes Actuator supply outputs AUX Operating conditions Ambient temperature [°C] -25...60 Protection IP 65 Tests / approvals EMC EN 50295 AS-i classification AS-i master profile M2; M3; M4 AS-i profile S-7.F.F AS-i I/O configuration [hex] 7 AS-i ID code [hex] F.F Data bits Data bit D0 D1 D2 D3 bidirectional I-1 / O-1 I-2 / O-2 I-3 / O-3 I-4 / O-4 Parameter bits Parameter bit Function P0 watchdog for all outputs : activated * / disabled P1 not used P2 not used P3 not used Mechanical data Weight [g] 317 Type of mounting AS-i interface to FC-E or SC lower parts Material PA 6-GF30; stainless steel (1.4305 / 303) Displays / operating elements Display Power LED, green Function LED, yellow Electrical connection Module connection Flat cable Remarks Remarks Inputs and outputs must be electrically isolated. Pack quantity 1 pcs. Electrical connection cage clamps: