Application Application field installation Electrical data Operating voltage [V] 26.5...31.6 DC Max. current consumption from AS-i [mA] 250 Reverse polarity protection yes Inputs / outputs Number of inputs and outputs Number of analog inputs: 2 Inputs Max. total current rating of inputs [mA] 200 Number of analog inputs 2; (Anschluss von 2- und 4-Draht-Sensoren) Analog input (current) [mA] 4...20 Operating conditions Ambient temperature [°C] -25...80 Storage temperature [°C] -25...80 Max. relative air humidity [%] 90; (non condensing) Max. height above sea level [m] 2000 Protection IP 67; (when flat cables are used E7400x / E7401x) Tests / approvals EMC EN 61000-6-2 EN 62026-2 EN 50581 MTTF [years] 167 UL approval voltage supply Class 2 AS-i classification AS-i version 2.11; 3.0 AS-i addressing IR addressing possible Extended addressing mode no AS-i master profile M3; M4 AS-i profile S-7.3.D AS-i I/O configuration [hex] 7 AS-i ID code [hex] 3.D AS-i certificate 99201 Mechanical data Weight [g] 277 Type of mounting AS-i flat cable connection Material PA; Socket: stainless steel (1.4404 / 316L); threaded inserts in the lower part: stainless steel (1.4404 / 316L); screws in the lower part: stainless steel (1.4578 / 316Cu); Piercing contacts: CuSn6 nickel-plated and tin-plated Displays / operating elements Display Power LED, green Voltage AS-i errors LED, red Function LED, yellow Channels AI1, AI2 Electrical connection Module connection Flat cable Accessories Accessories (optional) Protective cap: M12, E73004 stainless steel sleeve, for installation in case of high mechanical stress , E70402 Remarks Remarks The module is exclusively supplied via the yellow AS-i cable. When connecting a 2-wire or 3-wire sensor without own supply there has to be an external link between pin 3 and pin 4. The inputs (pins 2 and 4) are electrically separated and have no connection to AS-i. Pack quantity 1 pcs. Electrical connection Connector: M12; coding: A