Product characteristics Electrical design PNP Output function normally open / closed; (selectable) Sensing range [mm] 20 Housing rectangular Dimensions [mm] 40 x 40 x 120 Electrical data Operating voltage [V] 10...36 DC Current consumption [mA] 5; (24 V) Protection class II Reverse polarity protection yes Outputs Electrical design PNP Output function normally open / closed; (selectable) Max. voltage drop switching output DC [V] 2.5 Permanent current rating of switching output DC [mA] 250 Switching frequency DC [Hz] 300 Short-circuit protection yes Type of short-circuit protection yes (non-latching) Overload protection yes Monitoring range Sensing range [mm] 20 Real sensing range Sr [mm] 20 ± 10 % Operating distance [mm] 0...16.2 Accuracy / deviations Correction factor steel: 1 / stainless steel: 0.7 / brass: 0.4 / aluminum: 0.3 / copper: 0.2 Hysteresis [% of Sr] 1...15 Switch-point drift [% of Sr] -10...10 Operating conditions Ambient temperature [°C] -25...80 Protection IP 67 Tests / approvals EMC EN 61000-4-2 ESD 4 kV CD EN 61000-4-3 HF radiated 3 V/m EN 61000-4-4 Burst 2 kV EN 61000-4-6 HF conducted 3 V EN 55011 class B MTTF [years] 1727 UL approval Ta 0...40 °C Enclosure type Type 1 voltage supply Hazardous voltage File number UL E174191 Mechanical data Weight [g] 183.5 Housing rectangular Mounting non-flush mountable Dimensions [mm] 40 x 40 x 120 Material PPE Displays / operating elements Display Switching status 1 x LED, yellow Remarks Remarks 5 positions of the active zone possible Cut link to program as N.C. Pack quantity 1 pcs. Electrical connection - plug Connection Connector: 1 x M12; coding: A