AI-PMUL Universal Integrator for Rogowski Coils, Input (100 to 5000 Amp) and Output (0.333V,0.225V), and True RMS outputs (4-20mA,0-20mA,0-5V,0-10V), Adjustable Sensitivity(22.5,70,80,85,100,120mV/kA), Din Rail Mount
LEM AI-PMUL Universal Integrator for Rogowski Coils, Multi Range Input (100 to 5000 Amp) and Output (0.333V,0.225), and True RMS outputs (4-20mA,0-20mA,0-5V,0-10V), Adjustable Sensitivity(22.5,70,80,85,100,120mV/kA), Din Rail Mount The universal Rogowski coil integrator AI-PMUL complements LEM’s flexible clip-around coil ART and ARU range. The design is based on digital processing to give combined dynamic range, accuracy and versatility of use. It offers a wide range of output signals both True RMS and instantaneous. AI-PMUL is DIN rail mounted and can be stacked for multiphase application without spacing thanks to its low power dissipation. optional Input signal Accuracy Class 0.5 (IEC 61869-2) [1]. Linearity error ? 0.10 %. Protection degree IP2X. 35 mm DIN rail mounted. Push-in terminals. 4 selectable true RMS output signals: 0…20 mA, 4…20 mA, 0…5 V, 0…10 V. 2 selectable instantaneous output signals: 225 mV, 333 mV. 6 selectable sensitivities depending on Rogowski coil: 22.5, 70, 80, 85, 100, 120 mV/kA at 50 Hz. 12 selectable ranges: 100, 200, 300, 400, 500, 600, 800, 1000, 1500, 2000, 4000, 5000 A. Ambient operating temperature ?25...+70 °C. Advantages Compact design for DIN rail assembly High accuracy Class 0.5 (IEC 61869-2) Setup by user via Select / Edit buttons Clear status indication via bi-color led Applications MV/LV substations on LV side: Transformer Condition Monitoring Power metering: current measurement for active power calculation Building sub-metering: energy efficiency monitoring, consumption analysis and cost allocation Power quality monitoring: electrical loads and distribution system equipment Fault Detection, Isolation and Repair (FDIR): isolate the site of the fault Remote Terminal Units (RTU) Phasor Measurement Units (PMU) Standards IEC 61010-1: 2010 UL EMC: IEC 61326-1:2012 Options Cross power plugin connector: side contacts to stack up to 3 Integrator modules and use only one power supply. 24VDC Power Supply Meanwell HDR-15-24 Specification LEM Part Number AI-PMUL Function Integrator and True RMS Conditioner for Rogowski Coils Measuring Range Selectable 5000,4000,2000,1500,1000,800,600,500,400,300,200,100Amp Sensitivity Selectable 22.5,70,80,85,100,120mV/kA @ 50 Hz Output Selectable; Signal Conditioned True RMS 0-20mA, True RMS 4-20mA, True RMS 5V, True RMS 10V or 225mV, 333mV Direct Output (1 Amp output coming soon) Frequency Measuring Range 50-1500Hz (15th Harmonic) Operating Voltage 10-32VDC Accuracy 0.5% from 25 to 5000 Amp Current Consumption 100mA (max) Dimensions 100mm x 78mm x 15mm Mounting Din Rail Mount Integrator to Meter cable User Supplied Shielded cable 6mm sqr, up to 6m long Operating Temperature -25°C - 70°C Storage Temperature -45°C to 80°C Isolation (50Hz, 1 min) 1.5kV True RMS Response Time 160-190ms Termination Style Push-in for 1.5mm sqr wire Weight 58g Factory Pack Qty 1 Certifications UL, ROHS Datasheet Product Datasheet Application Notes User Notice 1) The Rogowski coil can measure any primary current as there is no saturation effect. 2) Not tested given that in the worst case (load = 0 Ohm i.e. short circuit on the output) the peak dissipated power remains low (< 2 Watts) 3) Frequency bandwidth and phase shift modelling schematic can be provided on request. 4) Referring to the main phase offset of 90 ° (a Rogowski coil is a derivative current transducer) 5) Considering a primary conductor of at least ? 15 mm, perpendicular and in contact with the Rogowski coil. 6) Considering an external conductor of at least ? 15 mm the same current level than internal conductor, perpendicular and in contact with the Rogowski coil.