The 460-100-SP is used on 95–120 V ac, 50*/60 Hz single-phase motors and the 460-200-SP is used on 190–240 V ac, 50*/60 Hz single-phase motors to protect them from damaging high and low voltage conditions. An adjustment knob allows the user to set a 1–500 second restart delay. The variable restart delay is also a power-up delay and can be utilized to stagger-start motors on the same system. A unique microcontroller-based, voltage-sensing circuit constantly monitors the voltage to detect harmful power line conditions. When a harmful condition is detected, the MotorSaver’s output relay is deactivated after a specified trip delay. The output relay reactivates after power line conditions return to an acceptable level and a specified amount of time has elapsed (restart delay). The trip delay prevents nuisance tripping due to rapidly fluctuating power line conditions. FeaturesProprietary microcontroller-based circuitryFixed trip delay 4 secondsAdjustable restart delay (1–500 s)Advanced LED indicationDIN-rail or surface-mountable *Note: 50 Hz will increase all delay timers by 20 % Pre-order 6-8 Weeks Specifications Input Characteristics Line Voltage 460-100-SP : 95–120 V ac460-200-SP : 190–240 V ac Frequency 50*/60 Hz Functional Characteristics Low Voltage (% of setpoint) Trip 90 % ±1 %Reset 93 % ±1 % High Voltage (% of setpoint) Trip 110 % ±1 %Reset 107 % ±1 % Trip Delay Time Low or High Voltage: 4 seconds fixed Restart Delay Time After a Fault: 1–500 seconds adjustableAfter a Complete Power Loss: 1–500 seconds adjustable Output Characteristics Output Contact Rating (1 Form C) Pilot Duty 480 VA @ 240 V ac, B300General Purpose 10 A @ 240 V ac General Characteristics Ambient Temperature Range Operating: -40° to 70°C (-40° to 158°F)Storage: -40° to 80°C (-40° to 176°F) Maximum Input Power 6 W Class of Protection IP20, NEMA 1 (finger safe) Relative Humidity 10–95%, non-condensing per IEC 68-2-3 Terminal Torque 4.5 in.-lbs. Wire Type Stranded or solid 12–20 AWG, one per termina Standards Passed Electrostatic Discharge (ESD) IEC 61000-4-2, Level 3, 6 kV contact, 8 kV air Radio Frequency Immunity, Radiated 150 MHz, 10 V/m Fast Transient Burst IEC 61000-4-4, Level 3, 3.5 kV input power and controls Surge IEC IEC 61000-4-5, Level 3, 4 kV line-to-line; Level 4, 4 kV line-to-ground ANSI/IEEE C62.41 Surge and Ring Wave Compliance to a level of 6 kV line-to-line Hi-potential Test Meets UL 508 (2 x rated V +1000 V for 1 min) Safety Marks UL UL 508 (File #E68520) Enclosure Polycarbonate Dimensions H 88.9 mm (3.5”)W 52.93 mm (2.084”)D 59.69 mm (2.35”) Weight 0.9 lb. (14.4 oz., 408.23 g) Mounting Method 35 mm DIN rail or Surface Mount (#6 or #8 screws)