The DCSA Series is a loop-powered, linear output current transducer that provides an output that is directly proportional to the RMS AC current passing through the LCSC10T12 sensor. The DCSA Series provides either an analog current or voltage: 4-20 mA, 1 to 5VDC, or 2 to 10VDC. Each unit is factory calibrated for monitoring (with the LCSC10T12 connected) in one of four ranges; 0-5, 0-10, 0-20, or 0-50A. Zero and span adjustments allow field calibration if needed. The DCSA Series mounts on both DIN 1 and DIN 3 rails. Operation The DCSA Series varies the effective resistance of its output in direct proportion to the current flowing in the conductor monitored by the LCSC10T12. Connecting the power supply to terminals C & D provides a 4 to 20mA DC current. Connect the power supply to terminals C & A to get 1 to 5VDC at terminal D. Connect the power supply to terminals C & B to get 2 to 10VDC at terminal D. FeaturesMounts on DIN 1 or DIN 3 rail0-50A in 4 ranges using LCSC10T12 sensorLoop powered from 10 to 30VDCLinear output from 4-20mA, 1-10VDCZero & span adjustmentsSeparate sensor & control unit *Minimum loop-power supply voltage equals the minimum sensor voltage 10VDC plus the voltage drop developed across all the other loop devices at 20mA. Specifications Input Ranges (without LCSC10T12 connected)4 factory calibrated ranges in mA AC 0 - 5mA, 0 - 10mA, 0 - 20mA, or 0 - 50mA AC Factory calibration ±0.5% of full scale Repeat Accuracy ±0.25% of full scale under fixed conditions Response Time ≅ 300ms Temperature Coefficient ±0.05%/°C Input to Output Not isolated Output Type Analog Current directly proportional to input current Range 4 - 20mA, or 1 to 5VDC or 2 to 10VDC Supply Voltage* 10 to 30VDC Momentary Voltage 40VDC for 1m Zero Adjust ≅ 3.75 - 4.25mA Span Adjust 18mA - 22mA Adjustment Mini-screw, multi-turn potentiometer Protection Dielectric Breakdown ≥ 2500V RMS terminals to mounting surface Insulation Resistance ≥ 100 MΩ Polarity Units are reverse polarity protected Mechanical Mounting DIN 1 & DIN 3 rail mounting Termination Wire clamp For 22 - 14AWG (.336 mm2 ... 2.5 mm2 ) Environmental Operating/Storage Temperature -30° to 60°C / -40° to 85°C Humidity 95% relative, non-condensing Weight ≅ 1.6 oz (45.4 g) Accessory - LCSC10T12 Toroidal Sensor Number of Turns 1000 Nominal Output Current Full Range 0 - 50 mA Maximum Allowable Current Steady 50A turns; Inrush 300A turns for 10s Burden ≤ 0.5 VA Frequency 0 - 20A / 21 - 50A 20/100 Hz / 30/100 Hz Sensor Hole 0.36 in. (9.14 mm) for up to #4 AWG (21.1 mm2 ) THHN wire Weight ≅ 1 oz (28.3 g)