Eastron Europe MCS-U22, Voltage Measurement Module for MCS Modular Metering System, U1,U2,U3,U12,U23,U31, Frequency, THD-U, and Alarm Threshhold, and RS485 Port 1/5 Amp CT Input RS 485 communication up to 38,400 bit/s True RMS values of Voltages, for Modular MCS system The module is intended for measuring, and monitoring single-phase or 3 phase electrical power network. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current, frequency, energy, power to the 30th Harmonic) from the measured signals. Features : Accuracy Class 0.5 Measurement of Current, Active and Reactive Power Modbus RTU communication up to 38,400 bit/s communication Specification Eastron Europe Part Number MCS-U22 Functions Three Phase / Single Phase Measurement Module for MCS Modular kWh Metering system Nominal CT Current Input N/A Tariff Input N/A Accuracy Class 0.5 (V) Mounting Din Rail Internal Memory N/A Dimensions 35mm x 90mm x 67mm (2 modules wide) Isolation 4kV RS485 2400-38400 b/s (400ms Response Time) Weight 150g Certification EN 61010-1 Installation Category III Factory Pack Qty 1 Enclosure Material Noryl with fire protection to UL94-V-O. Self extinguishing Enclosure Size 35mm (2 Modules) Operating Temperature -20 →+70 °C Documents Product Datasheet Modbus Utility EEM Meter Setting Software Utility