The PAD100-OROI uses one (1) SLC loop address when monitoring one (1) Class B circuit and providing one (1) Form C relay contact. The module mounts on either a 4" square or double gang box. The module is capable of monitoring one (1) Class B circuit. The PAD100- OROI includes one red LED to indicate the module's status. In normal condition, the LED flashes when the device is being polled by the control panel. When a the input is activated, the LED will flash at a fast rate. Application ThePAD100-OROI is compatible with Potter's IPA series addressable fire alarm control panels. The PAD100-OROI is an interface module used to monitor dry contact devices such as sprinkler waterflow, valve tamper switches, or conventional pull stations. The module is capable of monitoring one Class B circuit. The PAD100-OROI also provides one (1) form C relay contact. Setting the Address Each addressable SLC device must be assigned an address. The address is set using the DIP switch located on the PAD100-OROI. When the PAD100- OROI is used to monitor one Class B circuit a single device address is assigned, the input and relay are then identified as a sub-point of the module address. For example, if the address number is assigned as "8", the RLY1 relay will be "8.1" and the IN1 input will be "8.2" Main Features One (1) Class B monitoring input One (1) Form C relay contact SLC Class A, Class X & Class B Mounts in a standard 4" or double gang box Wiring terminals accessible when mounted in box All wiring terminals accept 22 to 12 AWG Product includes a 5 year warranty