MPN: 1910-5 Dwyer - Operating Pressure Range 1.4 - 5.5"wc Features: Service: Air and non-combustible, compatible gases Wetted Materials: Consult factory Temperature Limits: -30 to 180°F (-34 to 82.2°C) Pressure Limits: 45 in w.c. (11.2 kPa) continuous, 10 psig (68.95 kPa) surge Switch Type: Single-pole double-throw (SPDT) Repeatability: +/-3% Electrical Rating: 15 A @ 120-480 VAC, 60 Hz. Resistive 1/8 HP @125 VAC, 1/4 HP @ 250 VAC, 60 Hz. Derate to 10 A for operation at high cycle rates Electrical Connections: 3 screw type, common, normally open and normally closed Process Connections: 1/8" female NPT Mounting Orientation: Diaphragm in vertical position. Consult factory for other position orientations Set Point Adjustment: Screw type inside conduit enclosure Weight: 1 lb 4.5 oz (581 g) Agency Approvals: CE, CSA, FM, and UL. Optional-EXPL explosion-proof enclosure does not possess any agency approvals