Product Specifications Power and Network Power Consumption 45W maxSee Output Specifications table for load limits Power Input 10-36V DC input (via RS485) VLink Wireless Range Open field with line of sight: 300 ft / 90 mExpect reduced range indoors, depending on environment Uplink RS485 input Wireless Communication VLink sub-GHz transceiverWireless repeating not supported Inputs and Outputs Alarm Inputs 8x inputs with 12V DC aux powerCompatible with variable EOL resistors (1kΩ - 4.7kΩ) Conventional Fire Input (IDC) 1x 2-wire or 4-wire Initiating DeviceCircuit input (conventional) with switch-selectable 12/24V DC aux power RS485 Output 1x RS485 output with 36V DC aux power Relay Output 1x relay for siren/strobe/NAC with switch-selectable voltage & optional dry config: • 12 or 24V DC wet operation • 24V DC dry operation Addressable Fire Input (SLC) 1x 2-wire Signaling Line Circuit input (addressable) with 36V DC aux power Tamper Detection Yes General Dimensions (with enclosure) Height: 6.0" (15.3 cm)Width: 6.0" (15.3 cm)Depth: 1.9" (5.0 cm) Weight 1.6 lb (0.7 kg) Certifications FCC, IC, CE, UKCA, RCM, UL/IEC 62368-1, CSA NO22.2 62368-1 Operating Temperature and Humidity 32 to 122° F (0 to 50° C)0-90% RH non-condensing Warranty 10 years Installation Included Accessories 8x 1 kΩ EOL resistors, wall mount bracket, T10 Security Torx screwdriver, 4x machine screws, 4x wall screws, 4x wall anchors Mounting Options Wall or ceiling mount Product Resources Overview PDF Full Installation Guide