VX2-UMNA-A2T, Temp Controller, 48x96mm, 100-240VAC, Multirange Input, Relay Output, 2 Alarms, Retransmission Multirange Input (Programmable) 4-digit displays suit most industries including Temperature, Humidity, Pressure (0.5s response) Drip-proof / Dust-proof IP65 (front panel only) UL/CE Approved Input signals can be converted to insulated 4 to 20 mA DC output (for direct current output type) Each unit needs just 60 mm depth panel space EC Compliant Specification Hanyoung Nux Part Number VX2-UMNA-A2T Control Output 1 (Heat) Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4) Control Output 2 (Cool) N/A Input Multirange Type K/J/E/T/R/B/S/L/N/U/W/PLII/PT100/JPT100/4-20mA/0-20mA/1-5V/0-5V/0-10V/0-50mV/0-100mV. Note for Direct Current Input please use 250 Ohm Resistor in Parallel to the input terminals. Alarm Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4) Option 1 2nd Alarm Relay 3A(Resistive), 1A(Inductive load cos Ѳ=0.4) Option 2 PV/SV/MV retransmission Mounting Style 48 x 96mm Panel Mount Supply Voltage 85 - 265VAC Termination Style Screw Weight 350g Factory Pack Qty 1 ROHS Yes UL Yes CE Yes Datasheet VX Series Brochure VX Series Instruction Manual Free Software Hanyoung Nux TCS Software Hanyoung Nux TCS Software User Manual VX Series SB Driver (Windows 7) Not required for Windows 10 or 11