Product characteristics Probe length L [mm] 12 Process connection M12 x 1 Application Media Liquids; Gases Medium temperature [°C] -20...70 Pressure rating [bar] 30 Liquids Medium temperature [°C] -20...70 Gases Medium temperature [°C] -20...70 Electrical data Connection to control monitor VS2000 Exi (PTB 01 ATEX 2075) Measuring/setting range Probe length L [mm] 12 Liquids Setting range [cm/s] 3...300 Greatest sensitivity [cm/s] 3...60 Gases Setting range [cm/s] 200...2000 Greatest sensitivity [cm/s] 200...800 Accuracy / deviations Max. temperature gradient of medium [K/min] 15 Reaction times Response time [s] 1...10 Liquids Response time [s] 1...10 Gases Response time [s] 1...10 Operating conditions Ambient temperature [°C] -20...70 Protection IP 67 Tests / approvals Approval DMT 03 ATEX E091; IECEX BVS 06.0007 ATEX marking II 2G Ex ia IIC T4 Gb Shock resistance DIN IEC 68-2-27 40 g (11 ms) Vibration resistance DIN IEC 68-2-6 10 g (55...2000 Hz) MTTF [years] 8648 Safety classification Max. internal capacitance [nF] 1.2 Max. internal inductance [µH] 6 Temperature class T4 Mechanical data Weight [g] 346 Housing Threaded type Dimensions [mm] M12 x 1 Thread designation M12 x 1 Material stainless steel (1.4404 / 316L) Materials (wetted parts) stainless steel (1.4404 / 316L) Process connection M12 x 1 Installation length EL [mm] 27 Remarks Remarks In principle, the type test according to 94/9/EC (ATEX) only takes atmospheric conditions into account (0.8...1.1 bar). For pressures outside this range use must be assessed and approved by the user. Adhere to the operating instructions and the type test certificate. Pack quantity 1 pcs. Electrical connection Connection Cable: 6 m, TPE-S; Maximum cable length: 100 m; 5 x 0.34 mm²